Xianheng International (Hangzhou) Electrical Manufacturing Co., Ltd.
10kV Circuit Breaker Mechanical Characteristics Test Report

10kV Circuit Breaker Mechanical Characteristics Test Report

10kV Circuit Breaker Mechanical Characteristics Test Report
10kV Circuit Breaker Mechanical Characteristics Test Report
Talk to an expert

I. On-site Test Main Information


This report records a 10kV circuit breaker mechanical characteristics test performed at a 10kV power supply station using the HVS-50 circuit breaker analyzer.


1. Basic Information

Test date

2024.08.15

Tester

Gao Wenhao

Weather

Sunny

Location

A 10kV power supply station

Test sample type

Circuit breaker

Voltage level

12kV

Test item

Circuit breaker mechanical characteristics test

Instrument used

HVS-50


HVS-50 circuit breaker analyzer

Figure: HVS-50 circuit breaker analyzer

II. Test Procedure


Step 1: Test Preparation

The breaker tested in this case was not yet installed. First, locate the tripping and closing terminals on the breaker.


Step 2: Test Process

1. Ground the instrument and the breaker enclosure, then connect the time test lines in yellow-green-red sequence to the three-phase upper contacts of the breaker, with the lower contacts shorted and grounded.


Breaker contact wiring

Figure: Breaker contact wiring


2. Connect the instrument's close/trip and energy-storage output lines to the breaker close/trip coil and energy-storage coil terminals. On the aviation plug, the corresponding terminals are: close (4+, 14-), trip (31+, 30-); 14 and 30 are shorted; energy storage (35+, 25-).


Terminal wiring

Figure: Terminal wiring


3. Turn on the instrument and set the test duration and test voltage.

4. Select automatic test and click Test.

5. Perform the low-voltage action test: set the starting voltage (30% of the coil rated operating voltage), ending voltage, voltage rise mode, step size, and interval; turn on the DC power supply and click Test.


Step 3: Result Evaluation

The mechanical characteristics test analyzes closing time, three-phase synchronization, and bounce time for the closing test; opening time and three-phase synchronization for the opening test.


Opening test data

Figure: Opening test data


Closing test data

Figure: Closing test data

III. Test Summary


Regulations require that circuit breaker closing synchronization shall not exceed 5ms, opening synchronization shall not exceed 3ms, and closing bounce for breakers below 40.5kV shall not exceed 2ms. The breaker in this test was qualified. The opening/closing operating voltages were within requirements, so the breaker is qualified.

We are dedicated to providing our customers with reliable products and solutions.
We are dedicated to providing our customers with reliable products and solutions.
We look forward to discussing your needs, sharing our experiences, and collaborating to create a mutually beneficial partnership.Contact us now to start your collaboration today.
Get a Free Quote
Our representative will contact you soon.
* Your Name
* E-mail
* Phone/Whatsapp
Company
Country
* Message/Requirements
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. Part of the tracking is necessary to ensure SEO effectiveness,
By using this site, you agree to our use of cookies. Visit our cookie policy to learn more.
Reject Accept